Guangzhou Kebao insulation products Co., Ltd.




Русский
  • English
  • España
  • Français
  • Русский

Gel Cable Joints

Cast Resin Joints for Straight Connections

• Cast resin straight joint, LV — 7 sizes, OD 6 to 70 mm

• Cures solid: mechanical load, water pressure, no cable pull

• IP68 · 4×1.5 to 4×240 mm²

• Mould and pre-measured resin bag in every kit

Low voltage · 7 sizes · cable OD 6–70 mm · IP68 · two-part mould

Model: EU-S (S0-S6)

Sizes

7 (S0–S6)

Cable OD

<6 to 70 mm

Cores

1 to 4

Protection

IP68

Cast resin cable joint seals a connection inside a two-part mould filled with resin. Once the resin cures the joint becomes a solid block: it carries mechanical load, resists water pressure and does not move when the cable is pulled.

Seven sizes cover cable outside diameters from under 6 mm to 70 mm, and conductors up to 4×240 mm². Each size is supplied with the matching mould and a pre-measured resin bag, so there is no weighing on site.

Key features

  • Solid after curing — carries mechanical load and resists water pressure
  • Seven sizes — cable OD under 6 mm to 70 mm, to 4×240 mm²
  • Pre-measured resin — 80 g to 5000 g bags, no weighing on site
  • IP68 — buried, duct and underwater installation
  • Two-part mould — clip together, pour, demould after 2 hours
  • Low voltage — 1 kV class, single and multicore

Technical specifications

EU-S — technical data
Type Cast resin straight joint kit
Voltage class LV, 1 kV
Cores 1 to 4
Cable OD <6 – 70 mm
Conductor range 4×1.5 – 4×240 mm²
Degree of protection IP68 after curing
Demoulding time 120 min at 23 °C
Full cure 48 h at 23 °C
Kit contents Two-part mould, resin bag, gloves, instructions

Sizes and packs

Cast resin straight joints — size, cable OD, conductor range, mould and resin
Size Cable OD (mm) Conductor (mm²) Mould L/W/H (mm) Resin
S0 <6 — 100/18/18 —
S1 1 – 17 4×1.5 – 2.5 150/31/35 80 g
S2 8 – 26 4×1.5 – 10 185/40/45 160 g
S3 14 – 32 4×10 – 25 270/55/55 350 g
S4 23 – 39 4×35 – 50 355/65/60 600 g
S5 28 – 50 4×50 – 70 400/90/75 1250 g
S6 45 – 70 4×95 – 240 510/160/210 5000 g

S0 covers cable under 6 mm and is supplied without a resin bag. Other sizes on request.

Installation

  1. Fit the two mould halves around the completed connection and clip them closed.
  2. Seal the cable entries with the supplied tape or sealing strips.
  3. Mix the resin bag for 60 seconds, pour in one continuous stream and tap the mould to release air.
  4. Leave 120 minutes at 23 °C before demoulding; full cure is 48 hours.

Typical applications

  • Underground LV distribution
  • Direct buried feeders
  • Industrial cable trenches
  • Pump and submersible circuits
  • Joints that must resist cable pull

Compliance and working data

  • IP68 after curing
  • Low voltage 1 kV class
  • Demould 120 min / full cure 48 h at 23 °C
  • Resin supplied pre-measured per size

Ordering

  • Seven sizes: S0 to S6. State the cable OD and conductor size.
  • Resin bags are matched to the size; larger moulds are quoted on request.

Common questions

Why resin instead of gel?

Resin cures solid, so the joint carries mechanical load and holds under water pressure. Gel is faster but stays soft.

How long before backfill?

Demould after 120 minutes at 23 °C. Full cure takes 48 hours, but the joint can be backfilled once demoulded.

Which size for 4×25 mm²?

S3 covers 4×10–25 mm² at 14–32 mm cable OD.

Is the resin pre-measured?

Yes, each kit carries the bag matched to the mould, so nothing is weighed on site.